Modern inverters are equipped with a wide range of parameters, often numbering in the dozens or even hundreds. While many of these settings can be left at factory defaults for general use, some parameters are critical to the performance and safety of the system. These need to be carefully adjusted based on specific application requirements, as they may influence each other and affect overall operation.
For example, acceleration and deceleration time settings determine how quickly the motor speed increases or decreases. These times should be set to avoid overcurrent during acceleration and overvoltage during deceleration. Typically, it's best to start with longer times and gradually reduce them while monitoring the inverter’s response. This ensures smooth operation without triggering protective trips.
Torque boost, also known as torque compensation, is another important parameter. It helps maintain motor torque at low speeds by increasing the V/f ratio. Automatic settings can adjust this during startup, but manual tuning may offer better results for specific loads, especially those with variable torque characteristics. However, improper settings can lead to excessive energy consumption or poor performance.
Electronic thermal protection is designed to prevent motor overheating by calculating temperature rise based on current and frequency. This feature is most effective when used with one motor per inverter. In multi-motor setups, additional thermal relays are necessary.
The frequency limit function sets upper and lower bounds for output frequency, preventing damage from unexpected signal faults or over-speed conditions. It can also be used for speed control, such as limiting conveyor belts to a lower, more efficient operating speed.
Offset frequency allows adjustment of the base frequency when using external analog signals. Some inverters support polarity settings, enabling precise control over output frequency. Gain settings help match external signals with internal reference voltages, ensuring accurate frequency control.
Torque limits define the maximum drive and braking torque the inverter can apply. These settings help manage sudden load changes, reducing stress on the motor and inverter. Too high a setting may cause overvoltage, while too low may result in instability or repeated tripping.
Acceleration/deceleration curves, such as linear, nonlinear, or S-shaped, influence how the motor accelerates or decelerates. Choosing the right curve depends on the load type. For instance, S-shaped curves are ideal for constant torque applications, while nonlinear curves work well for fans or pumps.
Vector control enables precise motor control by separating stator current into magnetic and torque components. This method mimics DC motor performance, offering better efficiency and control, especially at low speeds. Most modern inverters use non-feedback vector control, eliminating the need for external speed feedback in many cases.
Energy-saving control is particularly useful for fans and pumps, where torque decreases with the square of speed. These inverters automatically adjust output voltage based on load, improving efficiency and reducing power consumption. However, enabling advanced features like torque vector or energy-saving control requires careful setup and compatibility checks.
Some users encounter issues when activating advanced functions, such as frequent inverter trips. This can be due to mismatched motor parameters, incorrect control mode settings, or improper parameter reading procedures. It's essential to verify all configurations before activation to ensure stable and safe operation.