When using RS485 or RS422 communication protocols, reversing the signal lines can cause the "1" and "0" signals to be inverted. If a converter is involved, the receiving end may always show a signal. In such cases, it's important to disconnect the converter from the device to test the connection properly.
a. For RS485 interfaces with built-in pull-up resistors, you can use a multimeter to measure the DC voltage between the D+(A) and D-(B) terminals. The voltage should be greater than 1V. By checking the polarity of the measured voltage, you can determine the correct direction: the positive terminal corresponds to D+(A), and the negative terminal corresponds to D-(B).
b. In RS485 networks without pull-up resistors, the voltage at both ends is typically a few hundred millivolts and usually less than 2V. You can still use the same method as described in (a) to determine the signal direction.
c. For RS422 networks, you can use the A and B modes on your multimeter to identify the correct signal direction. This helps ensure that the data is transmitted and received accurately.
These methods are essential for troubleshooting communication issues and ensuring proper signal integrity in industrial and embedded systems. Always double-check connections and use the right tools to avoid miscommunication or signal loss.